High energy igniter

Product Description

  Product Name: OYI instrument measurement and control ordinary high-energy igniter / ignition device
  Product details:
  [OYI instrument measurement and control of ordinary high-energy igniter / ignition device product structure]
  The general-purpose high-energy igniter/ignition device consists of three parts: the igniter, the ignition rod/ignition electrode and the shielded cable. It is mainly used in the ignition system of industrial burners.
  [OYI instrument measurement and control of ordinary high-energy igniter / ignition device working principle]
  When the igniter is working, the AC power frequency is 220V or 110V, which is converted into DC ripple current by boost rectification to charge the storage capacitor. When the capacitor is full, the discharge current is transmitted to the ignition rod/ignition electrode semiconductor nozzle through a discharge tube, a choke coil, a shielded cable, or the like to form a high-energy arc spark. When the ignition ignition is stopped, the remaining charge on the capacitor is discharged through the bleeder resistor.
  [OYI instrument measurement and control of ordinary high-energy igniter / ignition device features]
  The discharge voltage is low, the spark energy is large, the shape is small, the operation is convenient, the safety is reliable, the corrosion resistance, the service life is long, and the ignition energy requirement of a plurality of different fuels (including light oil and heavy oil) is met.
  [OYI measurement and control of ordinary high-energy igniter / ignition device application]
  Widely used in electric power, petrochemical, metallurgy, aviation, aerospace and other ignition fields. At present, the general-purpose high-energy igniter/ignition device of Eurometer has been used in many domestic power plants, and its performance is stable and reliable, which has been well received by users.
  [OYI instrument measurement and control of ordinary high-energy igniter / ignition device main technical parameters:]



  [OYI instrument measurement and control of ordinary high-energy igniter / ignition device product precautions]
  1. Do not energize the ignition device when there is no connection cable, ignition rod/ignition electrode;
  2. Check the ignition device before use, the connection should be correct, the contact is reliable, and the ignition rod/ignition electrode end of the ignition electrode extends into the fuel zone 100~200mm;
  3. The ignition device must cut off the system power during long-term shutdown;
  4. The ignition device must be repaired after the power has been turned off for 5 minutes. (Ensure that the remaining charge of the capacitor is drained through the bleeder resistor).
  [OYI measuring and controlling ordinary high-energy igniter / ignition device spare parts]
  1. High voltage ignition cable
  2. High-energy ignition rod / ignition electrode
  [OYI measurement and control of ordinary high-energy igniter / ignition device ordering instructions]
  1. Provide product model
  2. Product reference samples are available
Related Keywords:
Boiler Ignition System,High Energy Igniter,Ignition Cable,Ignition Gun,Ignition Oil Gun,Oil gun Swirl & atomizer,High energy ignition device,High energy ignition equipment,High energy ignition instrument,Boiler high energy igniter,Boiler igniter,Boiler ignition,Explosion-proof high-energy igniter,Explosion-proof high-energy ignition device,Portable high energy ignition device,Portable high energy igniter,Boiler ignition cable,High voltage shielded ignition cable,High voltage shielded ignition wire,Ignition lever,Ignition electrode,Ignition stick,Ignition discharge tube,High energy igniter discharge tube,Oil gun,Oil return ignition oil gun,Mechanical atomization ignition oil gun,Bubble ignition oil gun,Air atomizing ignition oil gun,Air atomized ignition oil gun,Steam atomized ignition oil gun,Steam atomization ignition oil gun,Ignition oil gun atomizer,Ignition oil gun swirl,Ignition oil gun oil separator
 
 